PT-510-SS-LC-HV - IEC 61850-3 managed DIN rail Ethernet switch, with 8 10/100BaseT(X) ports
Moxa's Layer 2 Managed Switches are characterised by industrial-grade reliability, network redundancy and security features based on the IEC 62443 standard. We offer robust, industry-specific products with multiple industry certifications, such as parts of the EN 50155 standard for railway applications, IEC 61850-3 for energy automation systems and NEMA TS2 for intelligent transport systems.
IEC 61850-3 managed DIN rail Ethernet switch, with 8 10/100BaseT(X) ports and 2 100BaseFX singlemode ports with LC connectors, 1 isolated power supply (88 to 300 VDC or 85 to 264 VAC), -40 to 85°C operating temperature
Details:
Ethernet interface
10/100BaseT(X) ports (RJ45 connection)
- 8
100BaseFX ports (single-mode LC connection)
- 2
standards
- IEEE 802.1D-2004 for Spanning Tree Protocol
- IEEE 802.1p for Class of Service
- IEEE 802.1Q for VLAN tagging
- IEEE 802.1s for Multiple Spanning Tree Protocol
- IEEE 802.1w for Rapid Spanning Tree Protocol
- IEEE 802.1X for authentication
- IEEE 802.3 for 10BaseT
- IEEE 802.3ab for 1000BaseT(X)
- IEEE 802.3ad for Port Trunk with LACP
- IEEE 802.3u for 100BaseT(X) and 100BaseFX
- IEEE 802.3x for Flow Control
Ethernet Software Features
Filter
- 802.1Q, GMRP, GVRP, IGMP v1/v2c, port-based VLAN, VLAN unaware
Industrial protocols
- EtherNet/IP, Modbus TCP
Management
- Back Pressure Flow Control, BOOTP, DHCP Option 66/67/82, DHCP Server/Client, Flow Control, HTTP, IPv4/IPv6, LLDP, Port Mirror, RARP, RMON, SMTP, SNMP Inform, SNMPv1/v2c/v3, Syslog, Telnet, TFTP
MIB
- Bridge MIB, Ethernet-like MIB, MIB-II, P-BRIDGE MIB, Q-BRIDGE MIB, RMON MIB groups 1, 2, 3, 9, RSTP MIB
Redundancy protocols
- MSTP, RSTP, STP, Turbo Chain, Turbo Ring v1/v2
Security
- HTTPS/SSL, TACACS+, Port Lock, RADIUS, Rate Limit, SSH
Time management
- NTP Server/Client, SNTP
Switch properties
IGMP groups
- 256
MAC table size
- 8 K
Max. Max. number of VLANs
- 64
Packet buffer size
- 1 Mbits
VLAN ID range
- VID 1 to 4094
Priority queues
- 4
Serial interface
Console port
- RS-232 (RJ45)
Input/output interface
Alarm contact channels
- Resistive load: 1 A @ 24 VDC
Power parameters
Connection
- 1 removable 5-contact terminal block(s)
Input voltage
- 110/220 VAC/VDC (88 to 300 VAC, 85 to 264 VDC)
Overload current protection
- Supports
Reverse polarity protection
- Supports
Input current
- 0.234/0.148 A @ 110/220 VAC
- 0.10/0.052 A @ 110/220 VDC
Physical properties
Housing
- Aluminium
Protection class
- IP40
Dimensions (without ears)
- 80 x 160 x 110 mm (3.15 x 6.30 x 4.33 in)
Weight
- 1210 g (2.69 lb)
Installation
- DIN rail mounting (with optional kit)
Ambient conditions
Operating temperature
- -40 to 85°C (-40 to 185°F)
- Note: Cold start requires at least 100 VAC @ -40°C
Storage temperature (including packaging)
- -40 to 85°C (-40 to 185°F)
Relative humidity
- 5 to 95% (non-condensing)
Standards and certifications
EMI
- EN 55032 Class A, CISPR 32, FCC Part 15B Class A
EMS
- IEC 61000-4-2 ESD: Contact: 8 kV; Air: 15 kV
- IEC 61000-4-3 RS: 80 MHz to 1 GHz: 35 V/m
- IEC 61000-4-4 EFT: Power: 4 kV; Signal: 4 kV
- IEC 61000-4-5 Surge: Power: 4 kV; Signal: 4 kV
- IEC 61000-4-6 CS: 10 V
- IEC 61000-4-8 PFMF
- IEC 61000-4-11 DIPs
Power Substation
- IEC 61850-3, IEEE 1613
Safety
- UL 508
MTBF
Time
- 372,276 hrs
Standards
- Telcordia SR332