MGATE 4101I-MB-PBS - 1-port Modbus-to-PROFIBUS slave gateway with 2 kV insulation
The MGate 4101-MB-PBS gateway provides a communication portal between PROFIBUS PLCs (e.g. Siemens S7-400 and S7-300 PLCs) and Modbus devices. With the QuickLink function, I/O mapping can be carried out within a few minutes. All models are protected by a robust metal housing, can be mounted on a DIN rail and offer optional integrated optical isolation.
1-Port Modbus-to-PROFIBUS slave gateway with 2 kV isolation, 12 to 48 VDC, 0 to 60°C operating temperature
Serial interface
- Console port: RS-232 (TxD, RxD, GND), 8-pin RJ45 (115200, n, 8, 1)
- Number of ports: 1
- Connector: DB9 connector
- Serial standards: RS-232/422/485
- Baud rate: 50 bps to 921.6 kbps
- Data bits: 7, 8
- Parity: None, Even, Odd, Space, Mark
- Stop bits: 1, 2
- Flow control: DTR/DSR, RTS/CTS
- RS-485 data direction control: automatic data direction control (ADDC)
- Pull high/low resistor for RS-485: 1 kilo-ohm, 150 kilo-ohm
- Terminating resistor for RS-485: 120 ohm
- Isolation: 2 kV (I models)
Serial signals
- RS-232c: TxD, RxD, RTS, CTS, DTR, DSR, DCD, GND
- RS-422: Tx+, Tx-, Rx+, Rx-, GND
- RS-485-2w: Data+, Data-, GND
- RS-485-4w: Tx+, Tx-, Rx+, Rx-, GND
Serial software functions
-Configuration options: MGate Manager
-Industrial protocols:
Modbus RTU/ASCII Master
Modbus RTU/ASCII Slave
PROFIBUS DP-V0 Slave
Modbus RTU/ASCII
- Mode: Master, Slave
- Supported functions: 1, 2, 3, 4, 5, 6, 15, 16, 23
- Max. Number of commands: 100
- Input data size: 7744 bytes
- Output data size: 7744 bytes
PROFIBUS interface
- Industrial protocols: PROFIBUS DP
- Number of ports: 1
- Connector: DB9 socket
- Baud rate: 9600 bps to 12 Mbps
- Isolation: 2 kV (built-in)
-Signals: PROFIBUS D+, PROFIBUS D-, RTS, Signal Common, 5V
PROFIBUS
- Rotary switch: PROFIBUS addresses 0-99 (addresses 100-125 are supported by software configuration)
- Mode: DP-V0 Slave
- Max. number of master connections: 1. Max. number of master connections: 1
- Max. Max. number of PROFIBUS I/O modules: 24 per page
- Max. number of PROFIBUS pages: 32 Max. number of PROFIBUS pages: 32
- Input data size: 7744 bytes
- Output data size: 7744 bytes
Power parameters
- Input voltage: 12 to 48 VDC
- Input current: 275 mA @ 12 VDC
- Power connection: Screwable Euroblock terminal
Relay
- Current carrying capacity of contacts: Resistive load: 1 A @ 24 VDC
Physical properties
- Housing: Metal
- Dimensions: 36 x 105 x 140 mm (1.42 x 4.14 x 5.51 in)
- Weight: 500 g (1.10 lb)
- IP rating: IP30
Note: It is recommended to fix the M3x3mm Nylok screws at the rear
Environmental limits
- Operating temperature: 0 to 60°C (32 to 140°F)
- Storage temperature (including packaging): -40 to 85°C (-40 to 185°F)
- Ambient relative humidity: 5 to 95% (non-condensing)
Standards and certifications
- EMC: EN 55032/35
- EMI: CISPR 32, FCC Part 15B Class A
- EMS:
IEC 61000-4-2 ESD: Contact: 6 kV; Air: 8 kV
IEC 61000-4-3 RS: 80 MHz to 1 GHz: 3 V/m
IEC 61000-4-4 EFT: Power: 2 kV; Signal: 1 kV
IEC 61000-4-5 Surge: Power: 2 kV; Signal: 2 kV
IEC 61000-4-6 CS: 150 kHz to 80 MHz: 10 V/m; Signal: 10 V/m
IEC 61000-4-8 PFMF
- Safety
IEC 60950-1
UL 60950-1
IEC 62368-1
UL 62368-1
- Potentially explosive atmospheres:
ATEX
Class I Division 2
IECEx
- Free-fall: IEC 60068-2-32
- Shock: IEC 60068-2-27
- Vibration:
IEC 60068-2-6
IEC 60068-2-64
MTBF
- Time:
MGate 4101-MB-PBS Models: 1.537,948 hours
MGate 4101I-MB-PBS models: 1,315,666 hours
- Standards:
Telcordia SR332