86M-4420-T - Module for the ioPAC 8600 series, 4 AOs, 0 to 10 V, -10 to 10 V, 0 to 20 mA

Deliverytime: 17 - 19 working days (Mo-Fr) *
653,79 EUR
Key points at a glance:
Product Description

Railway, wind power and offshore applications require system reliability and stability, even in harsh environments. Our ruggedised controllers and I/O products are designed for use in extreme conditions and offer versatile data acquisition and control functions.

Module for the ioPAC 8600 series, 4 AOs, 0 to 10 V, -10 to 10 V, 0 to 20 mA, or 4 to 20 mA, Operating temperature -40 to 75°C

Input/output interface
Analogue output channels
- 4
Isolation
- 3k VDC or 2k Vrms

Digital outputs
Connection
- spring euroblock terminal Spring Euroblock terminal
I/O mode
- DO or PWM

Analogue outputs
Connector
- Spring Euroblock terminal
I/O mode
- Static or waveform mode
Accuracy
- ±0.1% FSR @ 25°C
- ±0.3% FSR @ -40 to 75°C
Current load resistance
- External 24 VDC supply: 1000 Ohm
- Internal supply: 400 Ohm
Output range
- 0 to 10 VDC
- 0 to 20 mA
- -10 to 10 V
- 4 to 20 mA
Resolution
- 12-bit
Voltage output
- 10 mA (max.)
Waveform frequency
- 125 Hz
Waveform type
- sine, square, triangle

Power parameters
Power consumption
- 143.8 mA at 24 VDC

Physical properties
Dimensions
- 25 x 128.2 x 85.5 mm (0.98 x 5.05 x 3.37 in)
Weight
- less than 80 g
Cabling
- I/O cable, 16 to 28 AWG

Environmental conditions
Operating temperature
- -40 to 75°C (-40 to 167°F)
Storage temperature (in packaging)
- -40 to 85°C (-40 to 185°F)
Relative humidity
- 5 to 95% (non-condensing)
Altitude
- 2000 m

Standards and certifications
EMC
- EN 55032/24, EN 61000-6-2/-6-4
EMI
- CISPR 32, FCC Part 15B Class A
EMS
- IEC 61000-4-2 ESD: Contact: 6 kV; Air: 8 kV
- IEC 61000-4-3 RS: 5100 MHz to 6000 MHz: 3 V/m
- IEC 61000-4-4 EFT: Power: 1 kV; Signal: 0.5 kV
- IEC 61000-4-5 Surge: Power: 2 kV; Signal: 1 kV
- IEC 61000-4-6 CS: 10 V
- IEC 61000-4-8 PFMF
Railway
- EN 50121-4, EN 50155
Safety
- UL 508
Shock
- IEC 60068-2-27
Vibration
- IEC 60068-2-6

MTBF
Time
- 2,409.345 hours
Standards
- Telcordia SR332

This website uses cookies to ensure you get the best user experience. Privacy Policy