86M-2830D-T - Module for the ioPAC 8600 series with 8 DOs, 24 VDC, sink

Deliverytime: 17 - 19 working days (Mo-Fr) *
731,19 EUR
Key points at a glance:
Product Description

Railway, wind power and offshore applications require system reliability and stability, even in harsh environments. Our ruggedised controllers and I/O products are designed for use in extreme conditions and offer versatile data acquisition and control functions.

Module for the ioPAC 8600 series with 8 DOs, 24 VDC, sink, channel-to-channel isolation, channel LED, -40 to 75°C Operating temperature

Input/output interface
Digital output channels
- 8
Isolation
- 3k VDC or 2k Vrms

Digital outputs
Connection
- spring-loaded Euroblock terminal
Voltage
- 24 VDC 24 VDC
Rated current
- 200 mA per channel
I/O mode
- DO or PWM
I/O type
- sink
Overvoltage protection
- 41 VDC
Short circuit protection
- 750 mA @ 25°C
Pulse output frequency
- 1 kHz

Performance parameters
Power consumption
- 76.7 mA @ 24 VDC

Physical properties
Dimensions
- 25 x 128.2 x 85.5 mm (0.98 x 5.05 x 3.37 in)
Weight
- Less than 80 g
Cabling
- I/O cable, 16 to 28 AWG

Environmental conditions
Operating temperature
- -40 to 75°C (-40 to 167°F)
Storage temperature (in packaging)
- -40 to 85°C (-40 to 185°F)
Relative humidity
- 5 to 95% (non-condensing)
Altitude
- 2000 m

Standards and certifications
EMC
- EN 55032/24, EN 61000-6-2/-6-4
EMI
- CISPR 32, FCC Part 15B Class A
EMS
- IEC 61000-4-2 ESD: Contact: 6 kV; Air: 8 kV
- IEC 61000-4-3 RS: 5100 MHz to 6000 MHz: 3 V/m
- IEC 61000-4-4 EFT: Power: 1 kV; Signal: 0.5 kV
- IEC 61000-4-5 Surge: Power: 2 kV; Signal: 1 kV
- IEC 61000-4-6 CS: 10 V
- IEC 61000-4-8 PFMF
Railway
- EN 50121-4, EN 50155
Safety
- UL 508
Shock
- IEC 60068-2-27
Vibration
- IEC 60068-2-6

MTBF
Time
- 1.766.037 hours
Standards
- Telcordia SR332

This website uses cookies to ensure you get the best user experience. Privacy Policy