MGATE 5435-T - 4-port Modbus RTUASCIITCP-to-EtherNetIP gateways, -40 to 75C operating temperatu

Deliverytime: 17 - 19 working days (Mo-Fr) *
1.325,69 EUR
Key points at a glance:
Product Description
Whether single or multiple serial ports, Moxa’s Modbus TCP gateway solutions convert data in networks between Modbus RTU/ASCII, Modbus TCP, DNP3, CANopen, J1939, PROFIBUS, BACnet/IP, IEC 101/104, and IEC 61850, making configuration, troubleshooting, and conversion quick and easy.

4-port Modbus RTU/ASCII/TCP-to-EtherNet/IP gateways, -40 to 75°C operating temperature

Ethernet Interface
10/100BaseT(X) Ports (RJ45 connector)
- 2
- Auto MDI/MDI-X connection
Magnetic Isolation Protection
- 1.5 kV (built-in)

Ethernet Software Features
Industrial Protocols
- Modbus TCP Client, EtherNet/IP Adapter
Configuration Options
- Web Console (HTTPS), Device Search Utility (DSU)
Management
- ARP, DHCP Client, DNS, HTTP, HTTPS, SMTP, SNMP Trap, SNMPv1/v2c/v3, TCP/IP, UDP
MIB
- RFC1213, RFC1317
Time Management
- NTP Client

Security Functions
Authentication
- Local database
Encryption
- HTTPS, AES-128, AES-256, SHA-256
Security Protocols
- SNMPv3
- SNMPv2c Trap
- HTTPS (TLS 1.3)

Serial Interface
No. of Ports
- 4
Connector
- DB9 male
Serial Standards
- RS-232/422/485
Baudrate
- 300 bps to 921.6 kbps
Data Bits
- 7, 8
Parity
- None, Even, Odd, Space, Mark
Stop Bits
- 1, 2
Flow Control
- RTS Toggle (RS-232 only), RTS/CTS
RS-485 Data Direction Control
- ADDC (automatic data direction control)
Pull High/Low Resistor for RS-485
- 1 kilo-ohm, 150 kilo-ohms
- software configurable
Terminator for RS-485
- 120 ohms
- software configurable
Isolation
- 2 kV (built-in)

Serial Signals
RS-232
- TxD, RxD, RTS, CTS, DTR, DSR, DCD, GND
RS-422
- Tx+, Tx-, Rx+, Rx-, GND
RS-485-2w
- Data+, Data-, GND
RS-485-4w
- Tx+, Tx-, Rx+, Rx-, GND

Serial Software Features
Industrial Protocols
- Modbus RTU/ASCII Client

Modbus RTU/ASCII
Mode
- Client
Functions Supported
- 1, 2, 3, 4, 5, 6, 15, 16, 23
Max. No. of Server Connections
- 31
Max. No. of Commands
- 128 per serial port

Modbus TCP
Mode
- Client
Functions Supported
- 1, 2, 3, 4, 5, 6, 15, 16, 23
Max. No. of Server Connections
- 32
Max. No. of Commands
- 128
Total Output Data Size
- 4000 bytes
Total Input Data Size
- 4000 bytes

EtherNet/IP
Mode
- Adapter
CIP Objects Supported
- Identity, Message Router, Assembly, Connection Manager, TCP/IP interface, Ethernet link, Port
Max. No. of Scanner Connections
- 8 (read/write)
Input Data Size
- 496 bytes/connection (total: 3968 bytes) bytes
Output Data Size
- 496 bytes/connection (total: 3968 bytes) bytes

Memory
microSD Slot
- Up to 32 GB (SD 2.0 compatible)

Power Parameters
Input Voltage
- 12 to 48 VDC
Input Current
- 455 mA (max)
Power Connector
- Spring-type Euroblock terminal

Relays
Contact Current Rating
- Resistive load: 2 A @ 30 VDC

Physical Characteristics
Housing
- Metal
IP Rating
- IP30
Dimensions
- 42 x 90 x 130 mm (1.65 x 3.54 x 5.1 in)
Weight
- 403 g (0.89 lb)

Environmental Limits
Operating Temperature
- -40 to 75°C (-40 to 167°F)
Storage Temperature (package included)
- -40 to 85°C (-40 to 185°F)
Ambient Relative Humidity
- 5 to 95% (non-condensing)

Standards and Certifications
Safety
- EN 61010-2-201, UL 61010-2-201
EMC
- EN 61000-6-2/-6-4
EMI
- FCC Part 15B Class A
EMS
- IEC 61000-4-2 ESD: Contact: 8 kV; Air: 15 kV
- IEC 61000-4-3 RS: 80 MHz to 1 GHz: 10 V/m
- IEC 61000-4-4 EFT: Power: 4 kV; Signal: 2 kV
- IEC 61000-4-5 Surge: Power: 2 kV; Signal: 2 kV
- IEC 61000-4-6 CS: 150 kHz to 80 MHz: 10 V/m; Signal: 10 V/m
- IEC 61000-4-8 PFMF
Freefall
- IEC 60068-2-31
Shock
- IEC 60068-2-27
Vibration
- IEC 60068-2-6, IEC 60068-2-64

MTBF
Time
- 689,989 hrs