MGATE MB3660-8-J-2AC - Modbus gateway with two LANs, two AC mains inputs, 8 RS-232422485 ports

Deliverytime: 19 - 21 working days (Mo-Fr) *
1.623,39 EUR
Key points at a glance:
Product Description

Whether single or multiple serial interfaces, Moxa's Modbus TCP gateway solutions convert data on networks between Modbus RTU/ASCII, Modbus TCP, DNP3, CANopen, J1939, PROFIBUS, BACnet/IP, IEC 101/104 and IEC 61850, making configuration, troubleshooting and conversion quick and easy.

Modbus gateway with two LANs, two AC mains inputs, 8 RS-232/422/485 ports, serial RJ45 interface, 0 to 60°C operating temperature

Ethernet interface
10/100BaseT(X) ports (RJ45 connection)
- 2 IP addresses
- Auto MDI/MDI-X connection

Ethernet software functions
Industrial protocols
- Modbus TCP client (master)
- Modbus TCP server (slave)
Configuration options
- Web console (HTTP/HTPS) Web console (HTTP/HTTPS)
- Device Search Utility (DSU)
- MCC Tool
- Telnet console
Administration
- ARP
- DHCP Client
- DNS - HTTP - DHCP Client - DNS DNS
- HTTP
- HTTPS
- SMTP
- SNMP Trap
- SNMPv1/v2c/v3
- TCP/IP
- Telnet
- UDP
- NTP Client
- RADIUS
MIB
- RFC1213, RFC1317
Time management
- NTP client

Security functions
Authentication
- Local database
- RADIUS
Encryption
- HTTPS
- AES-128
- AES-256
- SHA-256
Security protocols
- SNMPv3
- HTTPS (TLS 1.2)

Serial interface
No. of ports Ports
- 8
Connector
- 8-pin RJ45
Serial standards
- RS-232/422/485 (software selectable)
Baud rate
- 50 bps to 921.6 kbps
Data bits
- 7, 8
Stop bits
- 1, 2
Parity
- None
- Even
- Odd
- Space
- Mark
Flow control
- RTS/CTS
- DTR/DSR
- RTS Toggle (RS-232 only)
Console connection
- RS-232 (TxD, RxD, GND), 8-pin RJ45 (115200, n, 8, 1)
Isolation
- 2 kV (I models)
RS-485 data direction control
- ADDC (automatic data direction control)
Pull high/low resistor for RS-485
- 1 kilo-ohm, 150 kilo-ohms
Terminating resistor for RS-485
- 120 ohms

Serial signals
RS-232
- TxD, RxD, RTS, CTS, DTR, DSR, DCD, GND
RS-422
- Tx+, Tx-, Rx+, Rx-, GND
RS-485-2w
- Data+, Data-, GND
RS-485-4w
- Tx+, Tx-, Rx+, Rx-, GND

Serial software functions
Industrial protocols
- Modbus RTU/ASCII Master
- Modbus RTU/ASCII Slave
Configuration options
- Serial console

Modbus RTU/ASCII
Mode
- Master, Slave
Supported functions
- 1, 2, 3, 4, 5, 6, 15, 16, 23
Max. Number of commands
- 256 per serial port
Memory size
- 65535 bytes

Modbus TCP
Mode
- client (master), server (slave)
Max. number of client connections - 256 per serial port No. of Client Connections
- 256
Max. No. of server connections
- 128
Supported functions
- 1, 2, 3, 4, 5, 6, 15, 16, 23
Max. number of commands - 256 No. of Commands
- 256
Memory Size
- 65535 Bytes

Modbus (Transparent)
Max. Max. number of client connections
- 256
Max. number of server connections - 128 Max. number of server connections
- 128

Power supply parameters
Input voltage
- Redundant dual inputs
- 100 to 240 VAC (47 to 63 Hz)
Number of power supply inputs
- 2
Power supply connection
- Terminal block (for DC models)
Current consumption
- 235 mA @ 110 VAC

Relay
Nominal contact current
- Resistive load: 2 A @ 30 VDC

Physical characteristics
Housing
- Metal
Protection class
- IP30
Dimensions (with ears)
- 480 x 45 x 198 mm (18.90 x 1.77 x 7.80 in)
Dimensions (without ears)
- 440 x 45 x 198 mm (17.32 x 1.77 x 7.80 in)
Weight
- 2600 g (5.73 lb)

Environmental conditions
Operating temperature
- 0 to 60°C (32 to 140°F)
Storage temperature (in packaging)
- -40 to 85°C (-40 to 185°F)
Relative humidity
- 5 to 95% (non-condensing)

Standards and certifications
EMC
- EN 55032/35
EMI
- CISPR 32, FCC Part 15B Class A
EMS
- IEC 61000-4-2 ESD: Contact: 6 kV; Air: 8 kV
- IEC 61000-4-3 RS: 80 MHz to 1 GHz: 10 V/m
- IEC 61000-4-4 EFT: Power: 1 kV; Signal: 1 kV
- IEC 61000-4-5 Surge: Power: 2 kV; Signal: 1 kV
- IEC 61000-4-6 CS: 10 V
- IEC 61000-4-8 PFMF
Free fall
- IEC 60068-2-31
Shock
- IEC 60068-2-27
Vibration
- IEC 60068-2-6
- IEC 60068-2-64

MTBF
Time
- 616.505 hours
Standards